NEWS

News

TAL22010 lightning protection device 1.2/50uS combined wave and 8/20uS current wave test

view:2025

Date:2017-09-15

On September 15, 2017, in accordance with customer requirements, our company conducted 1.2/50uS combined wave and 8/20uS current wave tests on the main product TAL22010 lightning protection device.
Product name (EUT): TAL22010 lightning protection device
Test Item: 1.2/50uS combined wave and 8/20uS current wave test
Equipment used: 10/700μs combined wave generator, 8/20uS surge test platform (80KA)
Test picture:


Test results: The actual impact resistance of TAL22010 is much higher than the design value: the nominal flow rate designed by AL22010 is 5kA, and the maximum flow rate is 10kA. The actual test uses 1.2/50us combination wave, 10kV surge impact 100 times (±50 times), the product is not damaged; With 8/20us current wave, 5kA surge impact 50 times (±25 times), the product is not damaged; use 8 /20us current wave, the product can withstand 10kA surge impact 4 times without being damaged, and it is only damaged at the 5th time. The actual ability to withstand the surge impact exceeds the design value.

Ruilongyuan Electronics, welcome everyone to come to our company for testing and communication. If you need to test, you can make an appointment with online customer service, www.ruilon.com.cn, thank you for your support to Ruilongyuan.



Back List